1
BOILER DESCRIPTION
1.1
INTRODUCTION
The cast iron boilers "GG GMP - GHP"
for gas-oil or gas has been designed in
compliance with the European Direc-
tives 2014/30/UE, 2014/35/UE, 92/42/
1.2
DIMENSIONAL DETAILS
560 (GMP) - 700 (GHP)
1.3
TECHNICAL FEATURES
1.3.1 "GG GMP" boiler
Output
Input
P (depth)
Sections
Maximum water head
Water content
Loss of head smoke
Comb. chamber pressure
Suggested chimney depression
Smokes temperature
Smokes flow
Adjustment range
Heating
Smokes volume
Weight
* Without baffles
22
CEE.
The components for "GG GMP -
GHP" installation are supplied in
three separate packages: boiler
body with smoke chamber disman-
tled and inserted in the combustion
125 (GMP)
135 (GHP)
M C.H. flow
R C.H. return
S
Boiler/filling drain 3/4"
GG GMP 6
GG GMP 7
kW
64.8
kcal/h
55,700
kW
73.4
kcal/h
63,100
mm
595
n°
6
bar
4
l
37.5
mbar
0.20
mbar
– 0.01
mbar
0.21
°C
225
3
m
n/h
68.0
°C
30÷85
3
dm
42
kg
261
chamber, casing with enclosed do-
cuments and control panel.
Instead, the boilers "GG GHP 6÷15S"
are supplied with the dismantled
boiler body.
P
R
GG GMP
GG GHP
1
"
2"
1 /
2
1
"
2"
1 /
2
3/4"
GG GMP 8
74.0
84.0
63,600
72,200
83.1
93.8
71,500
80,700
670
750
7
8
4
4
42.0
46.5
0.16*
0.22*
0.06
0.08
0.22
0.30
217
209
77.7
88.0
30÷85
30÷85
46
50
293
325
S
GG GMP 9
GG GMP 10
93.3
102.1
80,200
87,800
103.4
113.5
88,900
97,600
825
900
9
10
4
4
51.0
55.5
0.30*
0.35*
0.08
0.10
0.38
0.32
201
192
97.6
107.5
30÷85
30÷85
55
60
357
389
M