relay 2
1.
Position the unit so that it reads 3.50 m.
2.
Press 2 /
3.
Press 2 /
4.
Once installed, the unit will register a low alarm at 3.50 m from the sensor face. If
Loss of Echo
Applications
Pointek ULS200 is designed for use as a process level switch. The local display is used only as
an aid during start up. The instrumentation interface is comprised solely of the two relay
outputs. Switching applications are based on the relay functions adjustment.
Notes:
• All level setpoints must be within the device's range (3 m for solids, 5 m for liquids).
• Range applies to the device's switching capability, not to the process range of the
material.
The outputs can be set to function in the desired mode.
High / Low level switch
High level switch with two height alarms
Low level switch with two height alarms
High level switch with loss of echo alarm
Low level switch with loss of echo alarm
Pump down control with low level alarm
Pump down control with high level alarm
Pump up control with low level alarm
Pump up control with high level alarm
Pump down control with loss of echo alarm
Pump up control with loss of echo alarm
Pump up control and Pump down control
Dual pump down control
Dual pump up control
* Factory setting
Alarm: the relay de-energizes to set the alarm 'ON'
Control or Pump: the relay energizes to set the device 'ON'
Page EN-10
function display: pump up control
appears, complete steps 1 to 3 again.
Application
Pointek ULS200 – QUICK START MANUAL
Function
Relay 1
*1
High Alarm
2
High Alarm
3
Low Alarm
4
High Alarm
5
Low Alarm
6
Pump Down
7
Pump Down
8
Pump Up
9
Pump Up
10
Pump Down
11
Pump Up
12
Pump Down
13
Pump Down Pump Down
14
Pump Up
Relay 2
Low Alarm
High Alarm
Low Alarm
LOE Alarm
LOE Alarm
Low Alarm
High Alarm
Low Alarm
High Alarm
LOE Alarm
LOE Alarm
Pump Up
Pump Up
A5E32268616