4. Indicator lights and signal relay
The operating condition of the pump is indicated by the green and
red indicator lights in the pump terminal box, fig. 6.
Fig. 6
Green
Red
Indicator lights
Fault
Operation
(red)
(green)
Off
Off
Off
Permanently on
Off
Flashing
Permanently on
Off
Permanently on
Permanently on
Permanently on
Flashing
In case of a fault indication, the cause may be one of the fol-
lowing:
•
Too high motor temperature
•
Undervoltage
•
Overvoltage
•
Too many restarts (after faults)
•
Overload
•
Dry running
•
Other fault
A fault indication can be reset in one of the following ways:
•
By briefly opening the connection between terminals 2 and 3
(stops the pump).
•
By briefly switching off the electricity supply to the pump.
6
The pump incorporates an output for a potential-free signal via an
internal relay.
The functions of the two indicator lights and the signal relay are
as shown in the following table:
Contact position of
signal relay
The electricity supply has been switched off.
NO
NC
C
The pump is operating.
C NO NC
C NO NC
The pump has been set to stop.
C NO NC
The pump has stopped because of a fault. Restarting will be at-
tempted (it may be necessary to restart the pump by resetting the
fault indication).
C
NO
NC
The pump is operating, but it has been stopped because of a
fault.
C NO NC
The pump has been set to stop, but it has been stopped because
of a fault.
C NO NC
5. Megging
Note: Megging of an installation incorporating E-pumps is not al-
lowed, as the built-in electronics may be damaged.
Description