1 . About this document

– Please read carefully and keep in a safe place.
– Under copyright.
Reproduction either in whole or in part only with our consent.
– Subject to change in the interest of technical progress.
Symbols
!
Hazard warning!
Reference to other information in the document .
...

2 . General safety precautions

!
Disconnect the power supply before attempting any work on the sensor .
• During installation, the electric power cable being connected must not be live.
Therefore, switch off the power first and use a voltage tester to make sure the
wiring is off-circuit.
• Installing the sensor involves work on the mains power supply. This work must
therefore be carried out professionally in accordance with national wiring regu-
lations and electrical operating conditions. (e.g. DE-VDE 0100, AT-ÖVE-EN 1,
CH-SEV 1000)
3 . HF 3360
Proper use
– Sensor suitable for indoor wall and ceiling-mounting
The HF 3360 is an active motion detector. It responds to the slightest movement
regardless of temperature. The integrated HF sensor emits high-frequency electro-
magnetic waves (5.8 GHz) and receives their echo. In response to the slightest move-
ment in the detection zone, the change in echo is perceived by the sensor and a
motion detection message is sent to the bus.
Detection is possible through doors, panes of glass or thin walls.
Package contents for surface-mounted installation (Fig . 3 .1)
Package contents for concealed installation (Fig . 3 .2)
16
Product components (Fig . 3 .3)
A Connection module power supply lead, surface-mounted
B Connection module power supply lead, concealed
C Sensor module
D Designer trim, round or square
Product dimensions
Ceiling / wall mounting / surface-mounted and concealed wiring (Fig . 3 .4)

4 . Electrical installation

For wiring up the motion detectors, the following applies: under section 6 of VDE
0100 520, a multiple-core lead containing both the mains voltage leads and the
control leads (e.g. NYM 5 × 1.5) may be used for the wiring between sensor and DALI
Application Controller. The lead between DALI Application Controller and sensor must
be no longer than 300 m (for 1.5 mm²). After installing and switching ON, the sensor
flashes for 10 seconds.
Surface-mounted installation
If the rubber seal is damaged, the cable entry openings must be sealed with an M 16
or M 20 (at least IP 54) double seal cable gland.
5 . Mounting
• Check all components for damage.
• Do not use the product if it is damaged.
• Select an appropriate mounting location, taking the reach and motion detection
into consideration.
Installation procedure
Wall-mounting, concealed power supply lead (Fig . 4 .1)
Ceiling mounting, concealed power supply lead (Fig . 4 .2)
Wall-mounting, surface-mounted power supply lead (Fig . 4 .3)
Ceiling mounting, surface-mounted power supply lead (Fig . 4 .4)
For mounting on the wall, a water drainage hole (Ø 5 mm drill bit) is marked next to
the rubber seal. This must be opened if necessary. (Fig . 4 .3)
An optional corner wall mount is available for mounting the HF 3360.
(Prod. no. 035174 white).
• Switch OFF power supply . (Fig . 4 .1)
• Detach designer trim from sensor module.
• Disconnect sensor module from the connection module.
17