3.5 Connection to the webserver
The module can be configured by means of the
built-in webserver. To establish a connection from
a PC to CIM 500, proceed as follows:
1. Connect the PC and the module using an
Ethernet cable. See fig. 7.
2. Configure the Ethernet port of the PC to belong
to the same subnetwork as CIM 500, for example
192.168.1.101, and the subnet mask to
255.255.255.0. See section
IP address on your PC using Windows 7
to configure an IP address on your PC using
Windows
10.
3. Open a standard Internet browser and type
192.168.1.100 in the URL field.
4. Log in to the webserver:
User name
Default: admin
Password
Default: Grundfos
The first time you log in, you must set a
unique password. Only a factory resetting
of CIM 500 can reset the password to
Grundfos.
Fig. 7
CIM 500 connected to PC via
Ethernet cable
How to configure an
or
How
3.5.1 Connection to the webserver using GRM IP
To access the webserver via GRM IP, you need to
connect your PC parallel to the router (RJ45 port 1)
at CIM 500 RJ45 port 2. Look at the router
webserver which address the router assigns to the
CIM 500. Then use this IP address for the webserver
access.
See also sections
3.1 Security
configuration.
You can use both ETH1 and ETH2 to
establish a connection to the webserver.
You can access the webserver while the
selected Industrial Ethernet protocol is
active.
When you select "GRM IP", the connected
router automatically assigns an IP address
to the module via DHCP.
Fig. 8
CIM 500 connected to PC and
cellular router
and
Webserver
9