Installation Of Indoor Unit; External Dimensions - Toshiba MMD-VNK502HEX1E Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 27
5

Installation of indoor unit

WARNING
• Install the air conditioner at enough strong place to withstand the weight of the unit.
If the strength is not enough, the unit may fall down resulting in injury.
• To provide against strong wind or an earthquake, install the unit appropriately.
Inappropriate installation may result in the unit falling down and causing an accident.
NOTE
Strictly comply with the following rules to prevent damage of the indoor units
and human injury.
• Do not put a heavy article on the indoor unit. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit
unpacked by necessity, be sure to use buffering cloth, etc. to not damage the unit.
• To move the indoor unit, hold the hooking metals (4 positions) only.
Do not apply force to the other parts (refrigerant pipe, drain pan, foamed parts, or
resin parts, etc.).
Before you handle hanging brackets, put on thick gloves for protection.
• Supplied accessories are placed near the electrical control box. Do not dispose
of the accessories with the packaging. (See the figure on the right.)
• When a vibration-proof hanging bracket is attached to a hanging bolt, confirm that the unit does not vibrate more
through using the vibration-proof hanging bracket.
• Use a forklift to carry the unit. As it is packed in a cardboard box, do not drag or push it.
• Suction duct length must be longer than 850 mm.
• Helmet must be worn to protect your head from falling objects.
Especially, when you work under an inspection opening, helmet must be worn to protect your head from falling
objects from the opening.
 External dimensions
EA
(Exhaust air)
OA
(Outdoor air)
Inspection cover
Electrical control cover
115-EN
Box for supplied
accessories
A
J
RA
(Return air)
SA
(Supply air)
C
550
Maintenance cover
Model No.
MMD-VNK502HEX1E, VN502HEX1E
MMD-VNK802HEX1E, VN802HEX1E
MMD-VNK1002HEX1E, VN1002HEX1E
MMD-VNK1002HEX1E2, VN1002HEX1E2
Model No.
MMD-VNK502HEX1E, VN502HEX1E
MMD-VNK802HEX1E, VN802HEX1E
MMD-VNK1002HEX1E, VN1002HEX1E
MMD-VNK1002HEX1E2, VN1002HEX1E2
Center of gravity
G
Model No.
E
MMD-VNK502HEX1E
MMD-VNK802HEX1E
MMD-VNK1002HEX1E
MMD-VNK1002HEX1E2
MMD-VN502HEX1E
E
MMD-VN802HEX1E
MMD-VN1002HEX1E
MMD-VN1002HEX1E2
– 58 –
A
B
C
D
1,690
1140
1140
250
1,739
1189
1189
275
1,739
1189
1189
275
1,739
1189
1189
275
Duct
G
H
I
J
K
diameter
175
Ø195
Ø212
1601
1197
Ø200
200
Ø245
Ø262
1650
1246
Ø250
200
Ø245
Ø262
1650
1246
Ø250
200
Ø245
Ø262
1650
1246
Ø250
X
X
Y
Z
902
643
174
901
667
199
900
667
199
894
666
199
870
642
174
856
663
198
853
663
198
858
662
198
Unit: mm
E
F
175
350
200
400
200
400
200
400
Diameter of
Diameter of
refrigerant
refrigerant
piping at the
piping at the
gas side (L)
liquid side (M)
Ø9.5
Ø6.4
Ø12.7
Ø6.4
Ø12.7
Ø6.4
Ø12.7
Ø6.4
Z
Weight
91
111
112
114
84
100
101
103
116-EN