 How to check
To display an error code or to confirm the operation status, the remote controller (wired remote controller and
central remote controller) is equipped with an LCD display, and the interface circuit board of the outdoor unit is
equipped with a 7 segment display. A self-diagnosis function is activated to find out the details of a problem with
the unit.
 Error code list
The table below shows the error codes. See the table for details of error codes.
• To confirm the code from the remote controller, see "Wired remote controller display" in the table.
• To confirm the code from the outdoor unit, see "7 segment display on the outdoor unit" in the table.
Check code
Wired
remote
7 segment display on the
controller
outdoor unit
display
Auxiliary code
E01
E02
E03
E04
Number of indoor units for
E06
E06
normal reception
E07
E08
E08
Duplicate indoor addresses Duplicate indoor addresses
E09
E10
01: Indoor / Outdoor unit
communication
E12
E12
02: Communications
between outdoor units
E15
E15
00: Over capacity
E16
E16
01
~
: Number of connected
units
E18
00: No center unit
E19
E19
02: Multiple center units
01: Outdoor connections of
another line
E20
E20
02: Indoor connections of
another line
02: No header unit
E21
E21
00: Number of duplicate
header units
E22
E22
E23
E23
E25
E25
Number of outdoor units for
E26
E26
normal reception
E28
E28
Detected outdoor unit No.
159-EN
Check code name
Indoor unit - remote controller communication error (Detected by
remote controller)
Remote control transmission error
Indoor unit - remote controller communication error (Detected by indoor
unit)
Indoor / Outdoor unit communication circuit error (Detected by indoor
unit)
Number of indoor units decreasing
Indoor / Outdoor unit communication circuit error (Detected by outdoor
unit)
Duplicate header remote controllers
Indoor MCU communication error
Automatic address start error
No indoor unit during automatic address
Number of connected units / Over capacity
Indoor header - follower communication error
Unusual number of center outdoor units
Connections of another line during automatic address
Unusual number of thermal header units
Number of thermal units decreasing
Transmission error between outdoor units Number of thermal units error
(Reception error)
Duplicate terminal outdoor address settings
Number of connected outdoor units decreasing
Terminal outdoor error
Check code
Wired
remote
7 segment display on the
controller
outdoor unit
display
Auxiliary code
1
01 ○
02
03 ○
04
05 ○
06
07 ○
E31
E31
08
09 ○
0A
Judging
0B ○
device
0C
0D ○
0E
Remote
controller
0F ○
○: IPDU error
Remote
controller
F01
F02
Indoor
F03
Indoor
F04
F04
F05
F05
I/F
01: TE1 02: TE2
F06
F06
I/F
F07
F07
01: TE1 02: TE2
F08
F08
Indoor I/F
F10
F10
Remote
controller
F11
Indoor
F12
F12
01: Compressor 1
I/F
02: Compressor 2
F13
F13
03: Compressor 3
F15
F15
I/F
F16
F16
I/F
F17
F18
Indoor
F22
F22
I/F
F23
F23
F24
F24
I/F
F29
F31
F31
01: Compressor 1
I/F
H01
H01
02: Compressor 2
03: Compressor 3
I/F
01: Compressor 1
H02
H02
02: Compressor 2
I/F
03: Compressor 3
I/F
01: Compressor 1
H03
H03
02: Compressor 2
03: Compressor 3
I/F
H05
H05
I/F
H06
H06
H07
H07
– 80 –
Check code name
A3-IPDU
Fan IPDU
2
3
IPDU communication error
Indoor TCJ sensor error
Indoor TC2 sensor error
Indoor TC1 sensor error
TD1 sensor error
TD2 sensor error
TE1 sensor error
TL sensor error
TO sensor error
Indoor TSA sensor error
Indoor TFA sensor error
TS1 sensor error
TH sensor error
Miswiring of outdoor temperature sensor (TE, TL) error
Miswiring of outdoor pressure sensor (Pd, Ps)
Indoor TOA sensor error
Indoor TRA sensor error
TD3 sensor error
Ps sensor error
Pd sensor error
Indoor unit or other error
Outdoor EEPROM error
Compressor breakdown
Compressor error (Lock)
Current detection circuit error
Miswiring of outdoor discharge temperature sensor (TD1)
Low-pressure protection activation
Lower oil level detection protection
Judging
device
I/F
Indoor
Indoor
Indoor
I/F
I/F
I/F
I/F
I/F
Indoor
Indoor
I/F
IPDU
I/F
I/F
Indoor
Indoor
I/F
I/F
I/F
Indoor
I/F
IPDU
IPDU
IPDU
I/F
I/F
I/F
160-EN