Check code
Wired
remote
7 segment display on the
controller
outdoor unit
display
Auxiliary code
01: TK1 sensor error
02: TK2 sensor error
H08
H08
03: TK3 sensor error
04: TK4 sensor error
05: TK5 sensor error
H15
H15
01: TK1 oil circuit error
02: TK2 oil circuit error
H16
H16
03: TK3 oil circuit error
04: TK4 oil circuit error
05: TK5 oil circuit error
H25
H25
L02
L03
L04
L04
L05
Number of prior indoor
L06
L06
units
L07
L08
L08
L09
L10
L10
L20
Number of connected
L26
L26
thermal units
Number of connected
L27
L27
thermal units
L28
L28
A3-IPDU
Fan IPDU
1
2
3
01 ○
02
03 ○
04
05 ○
06
07 ○
L29
L29
08
09 ○
0A
0B ○
0C
0D ○
0E
0F ○
○: IPDU error
Detect indoor addresses
L30
L30
L31
P03
P03
01: Compressor 1
P04
P04
02: Compressor 2
03: Compressor 3
01: Open phase detected
P05
P05
02: Phase sequence error
161-EN
Check code name
Oil level detection temperature sensor error
Miswiring of outdoor discharge temperature sensor (TD2)
Oil detection circuit error
Miswiring of outdoor discharge temperature sensor (TD3)
Outdoor unit model mismatch error
Duplicate header indoor units
Duplicate outdoor line addresses
Duplicate prior indoor (Displayed for prior indoor)
Duplicate prior indoor (Displayed for non-prior indoor)
Group line in an individual indoor unit
Indoor group address not set
Indoor capacity not set
Outdoor capacity not set
Duplicate central control addresses
Number of connected thermal units exceeded
Number of connected thermal units error
Number of connected outdoor units exceeded
IPDU communication error
External interlock for indoor unit
Expanded I/C error
Discharge temperature TD1 error
High-pressure SW activation
Open phase detected, Phase sequence error
– 81 –
Check code
Wired
Judging
remote
7 segment display on the
device
controller
outdoor unit
display
Auxiliary code
01: Compressor 1
02: Compressor 2
P07
P07
I/F
03: Compressor 3
P09
P09
Detect thermal addresses
P10
P10
Detect indoor addresses
I/F
P13
P13
01: TS condition
P15
P15
I/F
02: TD condition
P17
P17
P19
P19
Detected outdoor unit No.
I/F
P20
P20
Indoor
0✽: IGBT circuit
Indoor
1✽: Position detection
I/F
circuit error
3✽: Motor lock circuit
I/F
4✽: Motor current detection
P22
P22
C✽: TH sensor error
I/F
D✽: TH sensor error
E✽: Inverter DC voltage
Indoor
error (Outdoor fan)
Note: 0 – F appears in "✽"
Indoor I/F
above. Ignore it.
Indoor
01: Compressor 1
I/F
P26
P26
02: Compressor 2
03: Compressor 3
Indoor
01: Compressor 1
I/F
P29
P29
02: Compressor 2
03: Compressor 3
I/F
P31
I/F
 Errors detected by TCC-LINK central control device
Check code
Wired
remote
7 segment display on the
controller
outdoor unit
display
Auxiliary code
I/F
C05
C06
C12
Depends on the error content of the
P30
alarmed unit.
Indoor
I/F
I/F
IPDU
I/F
Check code name
Heat sink overheat error
Thermal unit water shortage error
Indoor overflow error
Outdoor compressor liquid compression error
Gas leak detection
Discharge temperature TD2 error
Four-way valve reverse error
High-pressure protection activation
Outdoor fan IPDU error
G-TR short circuit protection error
Compressor position detection circuit error
Other indoor unit error (Follower unit error)
Check code name
Transmission errors of the TCC-LINK central control device
Reception errors of the TCC-LINK central control device
Simultaneous alarms for general-purpose device control interface
Follower unit error
Duplicate central control addresses
Judging
device
IPDU I/F
Thermal
Indoor
I/F
I/F
I/F
I/F
I/F
IPDU
IPDU
IPDU
Indoor
Judging
device
TCC-LINK
line
TCC-LINK
line
General-
purpose
device I/F
TCC-LINK
line
162-EN