Connection Of The Stator Cable - Philips SRO 2550 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

SRO 2550 ROT 350
5.2.3

Connection of the stator cable

Use a stator cable 7 x 0.82 mm².
Another type of stator cable 3 x 1.31 mm², screened has to be used only for connecting the
stator to the rotor control unit of a generator of the OPTIMUS/Velara family.
Note:
If using a generator of the OPTIMUS/Velara family earth the screening of the stator cable
with a metallic clamp.
Rotor control SRO
Figure 6: Stator connection
*) Generator of the OPTIMUS/Velara family only.
See
Place the jumpers across terminals XA 100 and XA 200.
figure 6
Connect the stator cable:
Table 1: Stator connection
SRO 2550 ROT 350
SRO_2550_ROT_350_Manual_English.fm
XA 100
U
1
4
3
6
5
8
7
9
V
W
*
Rotor
Cable
control
wire
1
SRO
2
3
2004 Philips Medical Systems
ALL RIGHTS RESERVED
XA 200
U
2
4
3
V
6
5
8
7
10
W
Connection
Phase
terminal
U
XA 101
V
XA 109
W
XA 202
(05.0)
XA
101
8
S4 = 22 Ω
107
7
115 mH
103
6
S3 = 22 Ω
109
5
115 mH
210
4
S2 = 18 Ω
204
3
68 mH
208
2
S1 = 18 Ω
202
1
68 mH
CMT_004
Stator data
phase/phase
11 Ω ± 10%
U - V:
57 mH ± 10%
9 Ω ± 10%
V - W:
34 mH ± 10%
17