Medicion De Las Resistencias De Final De Linea Con Energia De Salida Monitorizada (Sin Tension); Medicion De Las Resistencias De Final De Linea De Las Entradas Monitorizadas (Sin Tension); Chequear La Resistencia De Final De Linea En La Bus Rs485; Puesta En Marcha De La Fuente De Alimentacion - NSC Sicherheitstechnik Solution F1 Manual Del Usuario

Tabla de contenido

Publicidad

Measurement of the end of line resistors of the monitored power outputs
(without voltage)
Power
Key deposit box
output
1
depends on type
2
3
The end of line resistor has to be mounted in the last device of the power output cable. The adaptation
of open circuit and short circuit thresholds for the connected devices has to be done directly at the
FCP. Please go to "Installer" -> "more" (F3) -> "more" (F3) -> "Power outputs".
Measurement of the end of line resistors of the monitored inputs (without
voltage)
Input line
Key deposit box alarm
Extinguish interface
Checking the end of line resistor on the RS485 bus
End of line resistor activated at first and last device (jumper matched)?
Commissioning of the power supply
- plug 230VAC mains cable or check already plugged cable!
- switch on power supply for fire control panel!
The internal buzzer will be on: please switch off by pressing
NSC Sicherheitstechnik GmbH
Eckendorfer Str. 125 c
33609 Bielefeld
Sounder/flashlight Transmission device
1K/1W
tolerance 10%
-
1K/1W
tolerance 10%
-
1K/1W
tolerance 10%
End of line resistor
2,2K/0,5W
tolerance 10%
3,3K/0,5W
tolerance 10%
62/71
-
 fault
 ok
1K/1W
 fault
tolerance 10%
 ok
1K/1W
 fault
tolerance 10%
 ok
 fault
 ok
 fault
 ok
 o.k.  fault
Manual Solution F1- Español
Version S040A06.03
10.10.2012