6. Technical specifications:
SLAT PSU F40300-00 (24V 4A) for Solution F1-6 (Art. B01050-00)
Main AC voltage :
Operating voltage :
Operating voltage range:
Minimum output current:
Maximum permanent output current (Imax a) at 7 Ah:
Maximum permanent output current (Imax a) at 24 Ah:
Maximum peak current (Imax b):
Battery charging current:
Battery charging voltage:
Maximum battery capacity:
Minimum discharge voltage:
Ripple :
Operating temperature:
Humidity:
SLAT PSU F40305-00 (24V 6A) for Solution F1-18 (Art. B01060-00)
Main AC voltage :
Operating voltage :
Operating voltage range:
Minimum output current:
Maximum permanent output current (Imax a) at 7Ah:
Maximum permanent output current (Imax a) at 38Ah:
Maximum peak current (Imax b):
Battery charging current:
Battery charging voltage:
Maximum battery capacity:
Minimum discharge voltage :
Ripple:
Operating temperature:
Humidity :
NSC Sicherheitstechnik GmbH
Eckendorfer Str. 125 c
33609 Bielefeld
230V AC, +-15% , 50 – 60 Hz
27,2V +-2%
21,0V-28,2V
0 A
4,0 A – C/20*=3,65A (C=Battery capacity in Ah)
4,0 A – C/20*=2,8A (C=Battery capacity in Ah)
4,0 A
Max. 2,7 A
27,3 V (at 20°C)
7 Ah – 24 Ah
21,0 V
0,8 V pp
-5 to +40° C
Max. 95 % rel. Air humidity
230V AC, +-15% , 50 – 60 Hz
27,2V +-2%
21,0V-28,2V
0 A
6,0 A-C/20*=5,65A (C=Battery capacity in Ah)
6,0 A-C/20*=4,1A (C=Battery capacity in Ah)
6,0 A
Max. 4,5 A
27,3 V (at 20°C)
7 Ah – 38 Ah
21,0 V
0,8 V pp
-5 to +40° C
Max. 95 % rel. Air humidity
68/71
10.10.2012
Manual Solution F1- Español
Version S040A06.03