Common technical data
Maximum number of zones per loop
Maximum number of addressable devices per loop
Maximum number of zones per FCP
Maximum number of addressable devices per BMZ
Alarm activation equipment per FCP
Quiescent current of FCP without loop cards:
Quiescent current of loop card B01260-00 :
Quiescent current of loop card B01270-00 :
Quiescent current of conventional card B01300-00 :
Quiescent current of conventional card B01310-00 :
Quiescent current of relay card:
Operating temperature:
Humidity :
Housing :
Safety class:
Dimensions housing A1, A2 :
Weight FCP Solution F1-6 in housing A1, A2 :
Dimensions housing B1, B2 :
Weight FCP Solution F1-18 in housing B1, B2 :
NSC Sicherheitstechnik GmbH
Eckendorfer Str. 125 c
33609 Bielefeld
127
-
Hochiki: 127 detectors/modules + 127
base sounders
-
Apollo: 126 addressable devices
-
1024 programmable
-
192 LED indicator
-
Hochiki: 2286 detectors/modules + 2286
base sounders
-
Apollo: 2268 addressable devices
1
90 mA
33 mA (without detectors)
38 mA (without detectors)
30 mA (without detectors)
35 mA (without detectors)
4 mA
-5 to +40° C
Max. 95 % rel. Air humidity
Steel sheet, RAL 7035
IP 40
540 x 492 x 162 mm (W x H x D)
14 kg
540 x 540 x 245 mm (W x H x D)
18,5 kg