Interfaces
Thresholds for conventional zones
Functional tests
Test
Normal operation
- green LED „Operation" lights
- green LED „Night" lights
Fire condition
- Test of all automatic detectors
- Test of all manual call points
The fire condition can be generated in the installer
level by functions „test alarm" or „simulation".
Check display at FCP, remote panels and printer
Fault condition
- loop
- power outputs
- monitored inputs
- RS485 bus
- battery
- mains fault (mains fault delay)
Check display at FCP, remote panels and printer
Disabled condition
- detector
- zone
- power output
Check display at FCP, remote panels and printer
Alarm devices
- transmission device activation
- flash lights
- sounders
Fire outputs
- relays
- outputs
- output modules
Current of FCP at mains fault
Required bridge over time
Required battery capacity
NSC Sicherheitstechnik GmbH
Eckendorfer Str. 125 c
33609 Bielefeld
Configuration -> more
Configuration -> more
Measured value
..........
...............mA
.............h
............Ah
67/71
ok
not used
ok
not used
Test result
ok. fault
ok. fault
ok. fault
ok. fault
ok. fault
o.k. fault
o.k. fault
o.k. fault
Min
o.k. fault
o.k. fault
o.k. fault
ok. fault
ok. fault
ok. fault
ok. fault
ok. fault
ok. fault
ok. fault
ok. fault
10.10.2012