Minimum/ maximum voltages/currents
Output loop card analogue
-
voltage
-
current
Output conventional card
-
voltage
-
current
OC output
-
voltage
-
current
Power output
-
voltage
-
current
Relay
-
voltage
-
current
Input
-
voltage
-
current
Input extinguishing system
-
voltage
-
current
Input KDB sabotage
-
voltage
-
current
Fuse values
Power Supply Unit
-
mains
-
battery
-
external 24V
Main board
-
power output
-
FBC Output
Cable parameter
-
All installation cables
NSC Sicherheitstechnik GmbH
Eckendorfer Str. 125 c
33609 Bielefeld
27 - 35 Volt
0 - 250 mA
18 - 20 Volt
0 - 90 mA
0 - 30 Volt
0 - 50 mA
0,5 - 29 Volt
0 - 500 mA
0 - 30 Volt
0 - 1 A
0 - 30 Volt
0 - 0,5 mA
0 - 30 Volt
0 - 50 mA
0 - 30 V
0 - 50 mA
3,15 A time lag
6,3 A super fast
500 mA time lag
500 mA time lag
500 mA time lag
Fire system cable
JY-(ST)Y-2x2x0,8
70/71
10.10.2012
Manual Solution F1- Español