Dräger REGARD 3000 Instrucciones De Uso página 167

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Errors and mes-
sages
Transmitter
fault 1
.
.
Transmitter
fault 8
Warning Beam
block
Warning 1
transmitter
.
.
Warning 8
transmitter
Wrong REGARD
configuration
Measurement
range exceeded
Measurement
range underrun
Warmup trans-
mitter
Transmitter
maintenance
Special state 1
transmitter
.
.
Special state 8
transmitter
Configuration
warning
HART® not
working
|
Instructions for use
REGARD 3000
Cause
x
x
-
Transmitter not ready to
measure, it issues error
1 ... 8 depending on
system configuration
-
-
-
The beam path of the
transmitter is restricted
but the transmitter is
still ready to measure
-
-
-
Transmitter issues
warning 1 ... 8 accord-
ing to the system con-
figuration, but is still
ready to measure
-
-
-
Transmitter transmits
an unexpected warning
signal
-
-
-
Over range
-
-
-
Under range
-
-
x
Transmitter in warm-up
phase and not ready to
measure
-
-
x
Transmitter in mainte-
nance mode or in boot
phase and not ready to
measure
-
-
x
Transmitter issues the
special state 1... 8
depending on system
configuration and is not
ready to measure
-
-
-
At least one channel is
missing in configura-
tion for group message
(fault, alarm, warning,
maintenance, informa-
tion)
-
-
-
®
HART
communication
not working
Fault elimination and messages
Remedy
Check the transmitter
by remote access
®
(HART
) or locally. For
error details, see
instructions for use of
transmitter.
Check and, if neces-
sary, clean transmitter
beam path as directed
in instructions for use of
transmitter
Evaluate warning in
accordance with direc-
tions in instructions for
use of transmitter and
implement remedy
Set REGARD to detect
dynamic warning sig-
nals
n/a
n/a
n/a
n/a
n/a
Correct configuration of
group message
Check transmitter
installation
|