"SLEEPING WELL 1000" CAN BE USED BY ACTIVATING THE AIR CONDITIONING OR THE FAN FUNCTION ONLY.
T0 : TEMPERATURE SET BY USER
Tamb : AMBIENT TEMPERATURE DETECTED BY PROBE
V1 : COMPRESSOR ROTATION SPEED (2500 Rpm)
V2 : COMPRESSOR ROTATION SPEED (4000 Rpm)
The basic operating principles of the central control unit are:
About 30" after switching on, the ventilation starts up automatically.
The AC system can run for a maximum of 6 hours.
The display always shows the temperature set by the user (T0).
The temperature which can be set by the user is between 17°C and 28°C.
ON / OFF - TIMER BUTTON OPERATION
ON / OFF function:
When the system is switched off, pressing down this button for more than 2 seconds, switches on the AC system.
If the system is switched on, pressing down this button for more than 2 seconds, switches off the AC system.
Timer function:
If the system is switched on, every time the TIMER button is pressed quickly, the system operation time is reduced by 1 hour.
TURBO BUTTON OPERATION (offers maximum performance by the system)
When the system is running, (by default in mode V
hours and the whole snowflake symbol will light up on the display (despite being usually only half lit at speed V
Once this function has been activated, press the TURBO button again to return to speed V
By pressing the TIMER button with TURBO engaged, the compressor running time at speed V
If the fan increase or reduction buttons are pressed when the system is switched off, only the evaporator fan is activated, with the choice of 6
different speeds, shown on the central control unit display.
To switch off the fan it is necessary to set the value 0 on the central control unit display, using the fan speed reduction button.
The save-battery function starts when the power falls below a value of 21,5V.
In this case, the system (AC or VENT) shuts down, also deactivating the fan function and the message E1 appears on the display and the battery
symbol lights up.
When the power returns, for at least 10 seconds, to the value of 25V, the system is automatically reactivated, starting up the condenser fan,
followed by the evaporator fan and compressor.
Sleeping Well 1000_01_05/2007
Sleeping Well 1000_01_05/2007
CONDITIONING (AC)
) press the TURBO button to start rotation speed V
1
VENTILATION (FAN)
SAVE BATTERY FUNCTION (AC / FAN)
of the compressor for 4 consecutive
2
).
1
.
1
may diminish from 4 to 1 with steps of 1 hour.