★ Option 1:
There are 2 sets of low-voltage outputs (104/110/115/120V) on L1-N1 & L2-N2. Each set is able to provide 50% of UPS
rating power. Connect one load to L1-N1 and the other load to L2-N2.
★ Option 2:
After connecting L1&L2 and N1&N2, it becomes one low-voltage output (104/110/115/120V) at L1-N1 for 100% of UPS
rating power. Connect load to L1-N1 or L2-N2.
★ Option 3:
After connecting N1 and L2, it becomes one high-voltage output (208/220/230/240V) at L1-N2 for 100% of UPS rating
power. Connect load to L1-N2.
★ Option 4:
12
All manuals and user guides at all-guides.com
The output of ISO bank
The output of ISO bank
The output of ISO bank
The output of ISO bank