BATTERY
Battery type
Recharging voltage
Number
Standard Model
Typical Recharge Time
Charging current (max)
Backup time
Battery type and number
Charging current (max)
Long Backup time Model
Dimensions D x W x H (mm) - Battery bank
Weights (kgs) - Battery banks
INDICATORS
LCD Screen
ALARM
Battery Mode
Low Battery
Overload
Fault
MANAGEMENT / COMMUNICATION
Communication
Parallel connection
ENVIRONNEMENT
Humidity
Operating altitude
Noise Level
Heat dissipation max - HV (230 V)
NORMS
Standard
EMC ( Electromagnetic compatibility)
LVD (Safety)
SALES INFO
Warranty
Gencods - Standard versions cTUVus
Gencods - Long Backup time versions cTUVus
Gencods - Isolation transformer cTUVus
** When using internal batteries from 18-19, the unit will de-rate according to below formula : P=Prating x N/20
■Product specifications are subject to change without further notice.
INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - hotline@infosec.fr – 05 13 AA 59 206 14
All manuals and user guides at all-guides.com
E6 LCD RT EVOLUTION
TX 5000 (S)
7 hours recover to 90% capacity
635 x 440 x 133 (3U)
Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicator
USB & RS232 ports and Infopower included software ( support Windows family, Linux, Unix, and MAC)
less than 58 dBA @ 1 meter
600 W / 2047,8 Btu/h
3700085 67138 2
3700085 67142 9
3700085 67146 7
E6 LCD RT EVOLUTION
E6 LCD RT EVOLUTION
TX 6000 (S)
TX 8000 (S)
12 V / 7 AH
240 Vdc
20**
9 hours recover to 90% capacity
1A
From 4 to 30 minutes depending on the connected load
Depending on the capacity of external batteries
4A
635 x 440 x 133 (3U)
635 x 440 x 133 (3U)
59
Sounding every 4 seconds
Sounding every second
Sounding twice every second
Continuously sounding
Optional SNMP
Parallel port
0 - 95% relative humidity @ 0-40° non condensing
Up to 1000 m above sea level (>1000m 1% deterioration for every 100m)
less than 60dBA @ 1 meter
600 W / 2047,8 Btu/h
600 W / 2047,8 Btu/h
CE RoHS, cTUVus
EN 62040-2 : 2006
EN62040-1 : 2008, UL1778/R:2006;CSA C22.2 NO.107.3-05/R:2006
2 years
3700085 67139 9
3700085 67140 5
3700085 67143 6
3700085 67144 3
3700085 67146 7
3700085 67147 4
E6 LCD RT EVOLUTION
TX 10000 (S)
12 V / 9 AH
240 Vdc
20**
635 x 440 x 133 (3U)
65
600 W / 2047,8 Btu/h
3700085 67141 2
3700085 67145 0
3700085 67147 4
27