INFOSEC UPS SYSTEM E6 LCD RT Evolution TX 5 KVA Guia Del Usuario página 22

Ocultar thumbs Ver también para E6 LCD RT Evolution TX 5 KVA:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3) Output setting (only available or effective on bypass mode)
Interface
4) Battery setting (available on all operation modes)
Interface
22
All manuals and user guides at all-guides.com
Description
1. Volt:
208: Presenting the rated output voltage with 208Vac
220: Presenting the rated output voltage with 220Vac
230: Presenting the rated output voltage with 230Vac
240: Presenting the rated output voltage with 240Vac
2. Freq:
50Hz: The output frequency is setting for 50Hz.
60Hz: The output frequency is setting for 60Hz.
ATO: If selected, output frequency will be decided according to the latest normal
utility frequency. If it is from 46Hz to 54Hz, the output frequency will be 50.0Hz. If it
is from 56Hz to 64Hz, the output frequency will be 60.0Hz. ATO is default setting.
3. CVCF:
Enable or disable converter mode.
Enable: The output frequency will be fixed at 50Hz or 60Hz according to setting of
"Freq". The input frequency could be from 46Hz to 64Hz.
Disable: The output frequency will synchronize with the input frequency within
46~54 Hz for 50Hz system or within 56~64 Hz for 60Hz system.
NOTE: CVCF means Constant Voltage and Constant Frequency, it represents
converter mode.
Description
1. Dischg Protect:
1.1
Enable: Battery discharge protection function is enabled. When UPS have been
continuously working in "battery/battery test mode", the UPS will automatically
shut down when the running time set by option 1.2 below is up;
Disable: Battery discharge protection function is disabled.
1.2
0000~1500: The maximum discharge time ranging from 0 to 1500mins. UPS
will shut down to protect battery after backup time arrives when the "Dischg
Protect" is enabled. If "Dischg protect" is disabled, then this setting does not
make sense whatever the setting is; The default value for this setting is
990mins.
2. Batt Test Type:
2.1 Short Time: Battery test will last for 10 seconds.
2.2 Long Time: Battery test could last for longer time, which is able to be
adjusted within 01~99 minutes.
2.3 Till Batt Low: Battery test will not stop until battery voltage is low.
INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - hotline@infosec.fr – 05 13 AA 59 206 14

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

E6 lcd rt evolution tx 6 kvaE6 lcd rt evolution tx 8 kvaE6 lcd rt evolution tx 10 kvaE6 lcd rt evolution tx 5 kva sE6 lcd rt evolution tx 6 kva sE6 lcd rt evolution tx 8 kva s ... Mostrar todo

Tabla de contenido