INFOSEC UPS SYSTEM E6 LCD RT Evolution TX 5 KVA Guia Del Usuario página 31

Ocultar thumbs Ver también para E6 LCD RT Evolution TX 5 KVA:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

4)
Turn off the parallel system
Press and hold the "OFF" button to turn off the UPSs one by one. The buzzer will beep once. After a while, the UPSs
will enter to bypass mode or no output mode synchronously.
5)
Add one new unit into the parallel system
a)
You can not add one new unit into the parallel system when whole system is running. You must cut off the load
and shut down the system first.
b)
Make sure all of the UPSs are the parallel models and follow the connection refer to section 4.
c)
Install the new parallel system, please refers to the previous section.
6)
Remove one unit from the parallel system
a)
Press the "OFF" button twice. Then, the UPS will enter into bypass mode or no output mode without output.
b)
Turn off the output breaker of this unit. Then, turn off the input breaker of this unit.
c)
After it shuts down, you can move the parallel cable and share current cable. And then, remove the unit from the
parallel system.
INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - hotline@infosec.fr – 05 13 AA 59 206 14
All manuals and user guides at all-guides.com
31

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

E6 lcd rt evolution tx 6 kvaE6 lcd rt evolution tx 8 kvaE6 lcd rt evolution tx 10 kvaE6 lcd rt evolution tx 5 kva sE6 lcd rt evolution tx 6 kva sE6 lcd rt evolution tx 8 kva s ... Mostrar todo

Tabla de contenido