INSTALLER CONNECTIONS
Supplementary heating always enabled
Supplementary heating by boiler is enabled for all outside
air temperatures.
To enable heating at all times set parameter 0306 = 0 and
010h = 0
Boiler operation reflects the trend in water temperature, as
shown on the graph in figure 4.
3
Boiler
3°C
Enabled
OFF
0307 Outside temperature to
enable boiler
4
ON
Boiler
OFF
Outside air T
ON
Compressor
OFF
Once the boiler has been enabled, supplementary heating is activated when the
integration time set for parameter 0619 is reached and the delay time 0618 has
elapsed. The delay time is ignored when the unit is first started.
Example:
Value 0619 = 600°C*sec
Outlet temperature set point= 50°C
Actual temperature = 40°C
(50 – 40) x 60 sec = 600°Csec. ----> Boiler ON
Low values of 0619 mean frequent activation of the boiler.
Too high values of 0619 mean long delays in activating the boiler
Boiler operating parameters in SUPPLEMENTARY mode
when always ENABLED
Description
Activation Boiler
0 = Boiler not enabled
1 = Boiler enabled
Type of boiler operation
0 = Supplementary
1 = Replacement
Activation with low outside air
temperature
0 = Function not enabled
1 = Function enabled
Outside air temperature to enable
boiler
Minimum outside air temperature
for heat pump operation (make
sure the value set is the same as
shown in the table)
Boiler activation delay time (allows
the heat pump to reach steady
operation and thus avoid activat-
ing the boiler when not needed)
Integration time to activate boiler
Set the parameters following the sequence described in
the table
Boiler activation delay time 0618
Integration time 0619
U I A
Menu
Parameter
Value to be
UOM
no.
set
Mn03
0301
1
Mn01
010h
0
Mn03
0306
0
Mn03
0307
Example
-5°C
Mn03
0311
-20
Mn06
0618
60
Mn06
0619
600
°C*sec
System outlet temperature
set point
Actual water
temperature
System HP control
hysteresis
EN PBM 20÷40
°C
°C
min.
25