Operating Limits - Baxi PBM-i 20 Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

OPERATING LIMITS

HEATING
65
60
55
50
45
40
35
30
25
-25
-20
Operation in heating mode:
System circuit temperature difference, minimum 4°k, maximum 10°k
Maximum glycol content 40%
Maximum water inlet temperature at plate heat exchanger +50°C with temperature difference of 10°k
Minimum water inlet temperature at plate heat exchanger +22°C
COOLING
25
20
15
10
5
0
-5
-10
-15
-15
-10
Operation in cooling mode:
System circuit temperature difference, minimum 3°k, maximum 8°k
Maximum glycol content 40%
-15
-10
-5
0
5
Air intake temperature [°C]
-5
0
5
10
Air intake temperature [°C]
10
15
20
25
OPERATING RANGE
WITH WATER-GLYCOL MIXES
15
20
25
30
35
40
45
30
35
40
45
EN PBM 20÷40
I A
I A
50
50
35

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Pbm-i 30Pbm-i 40

Tabla de contenido