Outside air probe (BT11) connection
The outside air probe allows the system water temperature
set point to be compensated during heating or cooling opera-
tion.
Installation instructions
The outside air probe must be installed:
• outside of the home
• not in direct sunlight, away from flue gas discharges, air
outlets, or doors and windows.
• on a perimeter wall facing north/north-west
• at a minimum height of 2.5 metres above the ground or at
most half way up the house.
Installation procedure:
• Turn the probe cover inwards and remove it (1)
• Identify the correct installation position for the probe (see
"installation instructions)
• Fix the probe to wall at the correct height from the ground
(see the drawings), using the holes provided (2)
• Insert the connection cable in the cable gland on the probe
• Make the electrical connections as shown in figure (A-B),
also see the wiring diagram.
Make the connections according to the distance:
A. maximum distance 10 metres
B. maximum distance 100 metres
• Unscrew the two screws on the protective cover
and move dipswitch 7 to ON, see figure (3)
• Reposition the covers.