Pos. Terminal Description
Terminal for
alarm in case of
D1
too high stator
temperature
GND for alarm
in case of too
D2
high stator tem-
perature
Terminal for
alarm in case of
D3
moisture in the
motor
GND for alarm
in case of
D4
moisture in the
motor
16*
Output for alarm
D5
in case of insu-
lation fault
GND for alarm
D6
in case of
insulation fault
Terminal for
D7
warning
GND for
D8
warning
* See appendix Connection example DIGI-OUT IO111.
Data
Function
Digital output
24 VDC
Alarm in case of too high temperature in
min. 10 k
the stator windings. The output is
closed during normal operation.
If an alarm occurs, the connection is
broken between D1 and D2.
0 V
Digital output
24 VDC
Alarm in case of moisture in the motor
min. 10 k
part of the pump. The output is closed
during normal operation. If an alarm
occurs, the connection is broken
between D3 and D4.
0 V
Digital output
Alarm in case of too low insulation
24 VDC
value between stator windings and
min. 10 k
earth. The output is closed during
normal operation. If an alarm occurs,
the connection is broken between D5
0 V
and D6.
Digital output
Warning. The output is closed during
24 VDC
normal operation. If a warning occurs,
min. 10 k
the connection is broken between D7
and D8.
The following warnings can occur:
- communication warning
- configuration warning
- too much water in oil
0 V
- stator insulation resistance below
warning limit.
See also 8. Indication and 12. Fault
finding.
Diagram
D1
D2
D3
D4
D5
D6
D7
D8