BFT DEIMOS BT Instrucciones De Uso página 19

Ocultar thumbs Ver también para DEIMOS BT:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 41
11) ELECTRICAL INSTALLATION SETUP
Lay out the electrical installation as shown in fig.14 with reference to the CEI
64-8 and IEC364 provisions complying with the HD384 and other national
standards in force for electrical installation.
WARNING! For connection to the mains, use a multipolar cable having
a minimum cross section of 3x1.5 mm
standards. (For example, if the cable is not protected, it must be at least
equal to H07 RN-F, whereas if it is protected it must be at least equal
to H07 VV-F with a 3x1.5 sq mm
Connect the control and safety devices in compliance with the previously
mentioned technical installation standards.The cables (mains and auxiliary)
must be distinctly separated. Fig.14 shows the number of connections and
their cross sections for a length of approximately 100 metres; for greater
lengths, calculate the cross section for the true automation load.
The main automation components are (fig.14):
I
Type-approved adequately rated omnipolar circuit-breaker with at
least 3,5 mm contact opening, provided with protection against
overloads and short circuits, suitable for cutting out automation
from the mains. If not already install ed, place a type-approved
omnipolar circuit-breaker with a 0.03A threshold just before the
automation system.
QR
Control panel with built-in receiver
S
Key selector.
AL
Blinker with tuned antenna.
M
Actuator
P
Wall-mounted pushbutton panel.
Fte, Fre Pair of external photocells.
T
1-2-4 channel transmitter.
C
Sliding rack.
ANTENNA INSTALLATION
Use an antenna tuned to 433MHz.
For Antenna-Receiver connection, use RG8 coaxial cable.
The presence of metallic masses next to the antenna can interfere with radio
reception. In case of insufficient transmitter range, move the antenna to a
more suitable position.
12) TERMINAL CONNECTIONS
The cables must be held in position using an extra fixing device in the
proximity of the terminals, e.g. with cable clamps.
Also add more clips to the limit device wires, to the transformer primary
or secondary wires, and to the wires connected to the printed circuit.
During installation, the power supply cable must be stripped in order
for the earthing wire to be connected to the appropriate terminal, but
the active wires must be left as short as possible. The earthing wire
must be the last to stretch in the case where the cable fixing device
becomes loose.
WARNING: extremely low safety voltage cables must
b e p h i s i c a l ly s e p a r a t e d f ro m l ow vo l t a g e c a bl e s .
Access to the electrical compartment or to limit switches must be al-
lowed to skilled personnel only.
After adequate electric cables have been made to pass through the raceways
and the various automation components fixed to the chosen points, these
must be connected according to the instructions and diagrams shown in the
relevant instruction manuals. Connect the phase, neutral and earth (com-
pulsory) cables. The mains cable is to be secured in the appropriate cable
clamp (fig.15- ref. P1), the accessory cables in their cable clamp (fig.15- ref.
P2), and the protection (earth) wire, having a yellow/green insulating sheath,
must be held in its appropriate wire clamp (fig.15 - ref. S).
The automation device is to be set at work after all the safety devices have
been connected and checked. See the terminal diagram in fig.16.
JP2
1-2
Motor connection (1 Blue - 2 Red).
3-4
Transformer secondary circuit 24V.
WARNING – If the opening direction is not correct, reverse connec-
tions 1 and 2 for the motor and connections 6 and 7 for opening and
closing limit switches.
JP3
5-6
Closing limit switch SWC (5 Black common - 6 Red)
5-7
Opening limit switch SWO (5 Black common - 7 Brown)
8-9
Blinker 24V max 25W.
10-11 Antenna (10 signal - 11 braid)
12-13 Power supply for accessories:
24 V~ operation with power supply on
24 V
(12+,13-) operation with power supply off and optional battery
back up. Mod. SB BAT
14-15 Free contact (N.O.).
Gate-open warning light SCA (24V~ max 3W) or 2nd radio channel
output (see Fig.19-A)
The option can be set from the "logic menu" (see Fig.A).
INSTALLATION MANUAL
and complying with the current
2
cross section).
2
16-17 Output for power supply to safety devices (photocell transmitter and
safety edge transmitter)
N.B.: output only active during the manoeuvre cycle
24 V~ operation with power supply on
24 V
(16-,17+) operation with power supply off and optional battery
back up. Mod. SB BAT.
18-21 Input for safety devices FAULT (see item 13).
19-20 Pedestrian control button PED (N.O.) Opens the gate for 5 seconds
according to the logic set (2 or 4 steps).
21-22 START/CLOSE control button and key selector (N.O.).
The option can be set from the "logic menu" (see Fig.A).
21-23 STOP control button (N.C.). In all cases, stops the operator until the
next Start command. If not used, leave bridged.
21-24 Input for photocell PHOT (see item 13). If not used, leave bridged.
21-25 BAR electric edge contact input (N.C.).In case of triggering, movement
is stopped and reversed for about 3s. If not used, leave bridged.
21-26 OPEN control button (N.O.)
JP1
31-32 Transformer primary circuit 230V~.
33-34 Single-phase power supply 230V~, 50-60Hz (33N - 34L).
13) CONNECTION TO SAFETY DEVICES
Note: only use safety devices which can receive with a free changeover
contact (refer to Fig.19).
Refer to the diagram in fig. 19 for the connection of the inspected safety
devices, taking into account the number of pairs used: 1 pair box 1C, 2 pairs
box 2C, 3 pairs box 3C and 4 pairs box 4C. The control unit performs the
test of 3 or 4 safety devices only if provided with the additional SCS11-MA
board (see Fig. 21).The control unit performs the test of 2 safety devices.The
additional devices must be equipped with internal self-diagnosis and connected
in series. If photocells are not used, leave the jumpers aligned between terminal
21/23,21/24 and between terminal 21/25 of the QSC-D board.
14) PROGRAMMING
The control panel provided with a microprocessor is supplied with function
parameters preset by the manufacturer, suitable for standard installations.The
predefined parameters can be altered by means of either the incorporated
display programmer or UNIPRO.
In the case where programming is carried out by means of UNIPRO, carefully
read the instructions relating to UNIPRO, and proceed in the following way.
Connect the UNIPRO programmer to the control unit through the UNIFLAT
and UNIDA accessories (See fig. 17). The QSC-D control unit does not
supply the UNIPRO programmer with power, and therefore requires an
appropriate supply unit.
Enter the "CONTROL UNITS"menu, and the "PARAMETERS"submenu, then
scroll the display screenfuls using the up/down arrows to set the numerical
values of the parameters listed below.
For the function logics, refer to the "LOGIC" submenu.
In the case where programming is carried out by means of the incorporated
programmer, refer to Fig. A and B and to the paragraph on "Configuration".
N.B.: The QSC-D control unit cannot supply the UNIPRO programmer
with power.
15) CONFIGURATION
The display programmer is used to set all the QSC-D control panel func-
tions.
The programmer is provided with three pushbuttons for menu scrolling and
function parameter configuration:
+
menu scrolling/value increment key
-
menu scrolling/value reduction key
OK
Enter (confirm) key
The simultaneous pressure of the + and - keys is used to exit the active
menu and move to the preceding menu.
The modifications made are only set if the OK key is subsequently
pressed.
When the OK key is pressed for the first time, the programming mode is
entered.
The following pieces of information appear on the display at first:
-
Control unit software version
-
Number of total manoeuvres carried out (the value is expressed in
hundreds, therefore the display constantly shows 0000 during the first
hundred manoeuvres)
-
Number of manoeuvres carried out since the latest maintenance opera-
tion (the value is expressed in hundreds, therefore the display constantly
shows 0000 during the first hundred manoeuvres)
-
Number of memorised radio control devices.
When the OK key is pressed during the initial presentation phase, the first
menu can be accessed directly.
Here follows a list of the main menus and the respective submenus available.
The predefined parameter is shown between square brackets [ 0 ].
ENGLISH
19
DEIMOS BT-MA Ver. 11 -

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Qsc d ma

Tabla de contenido