Fine Offset Adjust - Mitsubishi AL2-10MR Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 460
α
2 Simple Application Controllers
13.4.6

Fine Offset Adjust

The fine adjust should only be performed after both Gain and Offset Adjusts have
been performed.
1) From the TopMenu, select "Others..."
2) From the Others... menu, select "Analog In"
3) From the Analog In menu, select the input for fine adjustment
4) Select "Offset fine" from the Analog Input settings menu.
5) Using the + and - buttons, enter a value from -15.5°C to 15.5°C (-27.9°F to 27.9°F) for a
PT100 input or -31°C to 31°C (-55.8°F to 55.8°F) for a TC input. Press the OK button when
finished.
AL2-2TC-ADP 13
T o pMe n u
C l o c k s e t
L ANGUAGE
O t h e r s . . .
O t h e r s . . .
S e r i a l
Com
L i g h t
T i me
A n a l o g
I n
A n a l o g
I n
I 0 1
I 0 2 : PT 1 0 0
I 0 3 : TC
I 0 2
Mo d e
Ca l i b r a t e
O f f s e t
f i n e
I 0 2
O f f s e t
f i n e
0 . 0 ° C
ENG-82

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Al2-14mrAl2-24mr

Tabla de contenido