Installation Height; Wall Mounting For Standalone/Network Monitor - Honeywell E3Point Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation Height

Detected Gas
CO
Carbon monoxide
H
S
Hydrogen sulfide
2
*NO
Nitrogen dioxide
2
O
Oxygen
2
COMB Most combustibles are heavier than air, with the exception of methane,
hydrogen, ethylene and acetylene. Sensors for gases that are heavier
than air should be installed approximately 30 cm (1 ft) from the floor. For
combustibles that are lighter than air, sensors should be installed 30 cm
(1 ft) from the ceiling, close to the potential leak source.
* May differ in certain applications. Hot NO
ambient air.

Wall Mounting for Standalone/Network monitor

1.
Verify that power to the monitor is off.
2.
While properly grounded for ESD protection, remove the PCBA from the
monitor. It is attached by a single center screw. Carefully place the PCBA
in the enclosed antistatic envelope.
3.
Drill two holes through the case and into the mounting surface;
horizontally if mounting on a vertical surface or vertically if mounting to a
standard electrical box as indicated below.
for mounting on electrical boxes
E
Point Gas Monitor Technical Manual
3
Relative Density Installation Height
(air = 1)
0.968
1.19
1.58 (cold)
1.43
2
3.28 in (8.3 cm)
1–1.5 m (3–5 ft.) from floor
30 cm (1 ft.) from floor
30 cm–1 m (1–3 ft.) from ceiling
1–1.5 m (3–5 ft.) from floor
from exhaust systems is lighter than
4 3/8 in (11.1 cm)
for mounting on
vertical survaces
Installation
5