Installation
4.
To mount the monitor, refer to the table for appropriate hardware and drill
size. Use the enclosed mounting template to drill into the vertical surface
if required.
Mounting
Surface
Drywall, Plaster,
Wood Paneling
Block, Brick,
Concrete
Electrical Box or
Duct
5.
Tighten the mounting bolts or screws to 8.7 in-lb (1 Nm) maximum.
6.
Remove the metal grounding plate before removing the knockouts.
7.
Remove one of the knockouts (depending on where cables will enter the
housing) and affix appropriate conduit.
8.
Run wiring through the conduit and the housing to the monitor, (See
wiring section).
9.
Reinstall the PCBA.
10. Install the sensor cartridge.
11. Complete wiring as shown in the
12. Close the cover and tighten the cover screws to 29.7 in-lb (3 Nm).
13. Restore power to the monitor.
6
Example
Part
Rounded head Toggle Bolt
QTY (2)
· 6-32
McMaster-Carr
· 3" long
#97121A013
· 1-1/2" wingspan toggle
· Pull Out Strength: 35 lbs
Metal Anchor for Block and Brick
QTY (2)
· 1" long
McMaster-Carr
· Pull out Strength: 60 lbs
#97026A021
AND
Rounded Head Screw
QTY (2)
·No. 6, 7 or 8 sheet metal or wood
McMaster-Carr
screw
#91555A111
· 2" long
As recommended by the manufacturer of the box or
Description
AND
duct
Wiring
section.
E
Point Gas Monitor Technical Manual
3