5 LCS-Tool
5.2.13 Start and Stop
To start and stop the Inverter Manager and inverters, use the [Start] and [Stop] buttons.
Figure 33: Inverter in operation (example)
Figure 34: Inverter in stop mode (example)
Procedure for stopping the system:
1. Open the LCS-Tool.
2. Log in as the user group User or Installer.
3. Select the [Stop] button.
☑ The [Start] button is displayed, The Inverter Manager
and inverters are stopped.
4. Open the Status > Inverters menu and observe the
current and voltage values of the inverters.
☑ The current and voltage output of the inverters is
reduced to zero. This process can take several minutes.
Procedure for starting the system:
1. Open the LCS-Tool.
2. Log in as the user group User or Installer.
3. Select the [Start] button.
☑ The [Stop] button is displayed, The Inverter Manager
and inverters are started.
4. Open the Status > Inverters menu and observe the
current and voltage values of the inverters.
☑ The current and voltage output of the inverters should
rise to the setpoint. This process can take several
minutes.
42
IMVIOBOX-IA-xx-19
5.2.14 Setting the Inverter Self-Test
"Q on Demand 24/7" Function
If the Q on Demand 24/7 function is enabled, the
inverter self-test must be set to a time when there is
enough PV energy available to start the inverters. If
the PV energy is not high enough to start the inverters,
no self-test will take place.
Tip: If the Q on Demand 24/7 function is enabled,
set the time of the self-test so that the inverter self-test
occurs during the day.
You can choose any time for the inverter self-test.
1. Open the LCS-Tool.
2. Log in as the user group Installer.
3. Select the Setup > Date and Time menu.
4. Enable the option button Selftest On/Off.
5. Set the desired time for the self-test.