DISPLAY
DESCRIPTION OF PERMANENT FAULTS (RESET)
Group
Specific
code
code
E.04
.10
Burner failed to ignite after 4 attempts
E.04
.12
Ignition failure for monitoring parasitic flame
E.04
.13
Fan blade blocked or maximum rpm exceeded
E.04
.17
Fault in gas valve control circuit
The flow temperature is below the minimum tempera­
E.04
.18
ture or the flow temperature sensor is not connected
E.04
.23
Communication internal stoppage
E.04
.29
Communication internal stoppage
E.04
.254
Fault in gas valve control circuit
Tab.52
List of warnings
DISPLAY
DESCRIPTION OF WARNINGS BEFORE A FAULT
Group
Specific
IS DETECTED
code
code
Solar temperature sensor is either removed or
A.00
.28
measures a temperature below range
Solar temperature sensor is either shorted or
A.00
.29
measures a temperature above range
Outdoor temperature sensor expected but not detec­
A.00
.34
ted
A.02
.06
Low pressure in heating circuit
A.02
.36
Functional device disconnected
A.02
.37
Passive functional device disconnected
A.02
.45
Connection error
A.02
.46
Device priority error
7804840 - 02 - 20012022
CAUSE – Check/Solution
An installer is required for most checks and solu­
tions.
GAS SUPPLY
Check the gas supply pressure
Check the gas valve electrical connection
Check the gas valve calibration
Check the operation of the gas valve
ELECTRODE PROBLEM
Check the electrode electrical connections
Check the electrode condition
OTHER CAUSES
Check the operation of the fan
Check the condition of the flue gas exhaust
(blockages)
Check the ground circuit
Check the power supply voltage
Check the electrode conditions
FAN/PCB PROBLEM
Check the PCB-fan connection
Check the fan operation
MAIN PCB ERROR
Check the electrical connections for the gas valve
SENSOR/CONNECTION PROBLEM
Check the sensor/PCB connection
Check the operation of the sensor
Switch the power supply off and on again and
then RESET
Switch the power supply off and on again and
then RESET
MAIN PCB ERROR
Check the electrical connections
CAUSE – Check/Solution
Check the solar temperature sensor wiring. Re­
place the sensor if necessary. In case of removal
of the solar tank, set the parameter DP150=1.
Check the solar temperature sensor wiring. Re­
place the sensor if necessary.
OUTDOOR SENSOR NOT DETECTED
Enter the correct value of the parameter AP091
Connect the outdoor sensor
Outdoor sensor is not connected correctly
Check the installation pressure and restore
Check the expansion vessel pressure
Check for boiler/installation leaks
COMMUNICATION FAULT
Start the auto-detect function (parameter AD)
Check the devices connected to contact X9
COMMUNICATION FAULT
Start the auto-detect function (parameter AD)
Check the devices connected to contact X9
COMMUNICATION FAULT
Start the auto-detect function (parameter AD))
COMMUNICATION FAULT
Start the auto-detect function (parameter AD))
en
8 Troubleshooting
INIDENS
65