6.4 Operating test

Press the control button and close the window, checking that:
A. The window is completely closed. If it is not, check that the gap between the window and the frame is bigger than
or equal to 0 mm. If necessary, insert spacers so as to obtain the correct gap.
B. The chain is perfectly vertical to the window frame. If necessary adjust the fixing bracket by using the screws and
slots.
Having reached the correct closing position, press the control button and open the window in order to check that the
actuator runs freely over the full travel set up.
Having achieved the required opening run, press the control button again to close the window. Once the window
has completely closed, check that the screws, supports and fixings are tightened correctly, and that the seals are
sufficiently compressed.
Bottom-hung inward opening window:
CAREFUL!! - after installation the 4 covers must be perfectly closed.
Insert the rubber DIP-switch cover and close the end cap
Installation completed