The content of this chapter should be thoroughly read and un-
derstood since it describes methods of measurements and basic
principles of interpreting measurement results.

5.1 Current measurement

WARNING:
Disconnect the test leads before measuring current us-
ing clamp.
To perform the current measurement:
 set the rotary switch at 60A
 press MODE/VFD button to display the following symbol:
, if you are measuring alternating current,
, if you are measuring direct current,
 use the clamp-opening trigger
tested conduit. Only one conduit must be within the testing range
of the clamps,
 read the measurement result on the display.

5 Measurements

/ 600A
CMP-1015-PV – USER MANUAL
/ 1000
A,
and attach the clamps on the
53