Use the arrow keys to select the required parameter and edit the parame-
•
ter value.
Use the ENT key to confirm the selected parameter and the parameter
•
values entered.
The rated data of the motor are to be entered according to the speci-
fications on the rating plate for the motor connection type used (star
or delta connection). If the data entered deviate from the rating plate,
the parameters will not be identified correctly. The rated data is to be
parameterized as per the motor rating plate. Consider the increased
rated current of the connected three-phase motor when the motor is
switched from star to delta.
After input of the machine data, the calculation or exami-
GB
nation of the parameters is automatically started. The
display changes over to "CALC" for a short time. If the
verification of the entered machine data is successful, the
guided commissioning procedure continues with the identi-
fication of the parameters (automatic measurement of
further machine data).
•
Note the warnings and error messages displayed during guided commis-
sioning.
To ignore the warning messages, press the ENT key. The guided commis-
•
sioning is continued. However, it is recommended that the data be
checked and corrected if necessary.
To correct the entered parameter values after the warning or error mes-
•
sage, press the ESC key. Use the arrow keys to switch to the parameter
value which is to be corrected.
Further machine data are measured while the drive is at a
standstill. These measurements will be entered automatical-
ly in the relevant parameters by the parameter identifica-
tion feature.
•
Confirm the display "PAidE" by pressing the ENT key.
Note the warnings or error messages upon completion of the parameter
•
identification.
No signals at digital inputs S1IND (STOA) and S7IND
(STOB). If signals were already applied at the beginning of
the guided commissioning, the "StO" message is not dis-
played.