03 Phase failure, check motor and wiring.
F05 00 Overloaded, check load situation and ramps.
03 Short circuit or earth fault, check motor and wiring.
05 Asymmetric motor current, check current and wiring.
06 Motor phase current too high, check motor and wiring.
07 Message from phase monitoring, check motor and wiring.
F07 00 DC link voltage too high, check deceleration ramps and connected
brake resistor.
01 DC link voltage too low, check mains voltage.
02 Mains failure, check mains voltage and circuit.
03 Phase failure, check mains fuse and circuit.
GB
04 Mains voltage UDC too high when turned on, check voltage.
05 Mains voltage BC too high when turned on, check voltage.
06 Mains voltage MC too high when turned on, check voltage.
F08 01 Electronics voltage too low, check control terminals.
04 Electronic voltage too high, check wiring of control terminals.
F11 00 Output frequency too high, check control signals and settings.
01 Max. frequency reached by control (voltage control), check decelera-
tion ramps and connected brake resistor
F12 01 Diagnosis error of function STO; at least one of the shut-down paths
STOA and STOB is defective. Check the devices connected to the
shut-down paths; check wiring and EMC.
04 Software self-diagnosis has detected an internal error. Parameter
Error Environment 1
BONFIGLIOLI customer service.
05 Fault message of 5-second monitoring. Shut-down paths STOA and
STOB were not actuated at the same time, but with an offset of
more than 5 seconds. Check addressing of shut-down paths or con-
trol of protection provision.
F13 00 Earth fault at output, check filter and cabling.
10 Minimum current monitoring, check motor and wiring.
F14 01 Reference value on multifunction input 1 faulty, check signal.
07 Overcurrent on multifunction input 1, check signal.
126
Output current
DC-Link Voltage
Electronic voltage
Output frequency
Safety function STO
262 describes the cause of the error.. Consult
Motor connection
Control connection