When the system signal of the photovoltaic inverter and water temperature in the tank is less than
60℃, heat pump will heat up water until 65℃.
Note: Photovoltaic cycle can be activated or deactivated on control panel, default is deactivated, refer
to configuring parameters table.
4) Solar pump circulation cycle
When Solar collector temperature≥30℃, and solar collector temperature≥tank water
temperature +7℃,start the solar pump.
When Solar collector temperature<30℃,or solar collector temperature≥120℃,or solar
collector temperature≤tank water temperature +4℃,stop the solar pump. Continuously detect solar
collector temperature and tank water temperature.
Note: Solar pump circulation cycle can be activated or deactivated on control panel, default is
deactivated, refer to configuring parameters table. This function is optional.
5) E-Anode function
The appliance is equipped with a magnesium anode, the E-Anode (impressed current anode) is
optional.
Note: E-Anode function can be activated or deactivated on control panel, default is activated, refer to
configuring parameters table. This function is optional.
21