INSTALLATIoN
Commissioning
13. Commissioning
Our customer support can assist with commissioning, which is a
chargeable service.
If the appliance is intended for commercial use, observe the rules
of the relevant Health & Safety at Work Act during commissioning.
For further details, check with your local authorising body (in
Germany, for example, this is the TÜV).
13.1 Checks before commissioning the heat pump
manager
Material losses
!
Observe the maximum system temperature in underfloor
heating systems.
f Check that the heating system is filled to the correct pressure
and the quick-action air vent valve is closed.
f Check whether the outside temperature sensor is correctly
placed and connected.
f Check whether the power supply is connected correctly.
f Check whether the signal cable to the heat pump (bus cable)
is correctly connected.
High limit safety cut-out
Note
At temperatures below –15 °C the high limit safety cut-out
may respond. The appliance may be subjected to these
temperatures during storage or transport.
1 High limit safety cut-out reset button
f Check whether the high limit safety cut-out has tripped.
f If the high limit safety cut-out has triggered, reset it with the
reset button.
www.stiebel-eltron.com
13.2 Commissioning the heat pump manager
Commission the heat pump manager and make all settings in ac-
cordance with the heat pump manager operating and installation
instructions.
Note
For DHW mode, ensure that the PARALLEL OPERATION
option is set in the heat pump manager. With this setting
the primary pump is also active in DHW mode.
To set the heat pump manager:
f With the MENU key, call up the main menu.
f Select the menu or value and confirm with OK:
SETTINGS
DHW

STANDARD SETTING

DHW MODE
Note
On appliances with a single phase connection, set the
heat pump manager as follows for calculating the amount
of heat.
To set the heat pump manager:
f With the MENU key, call up the main menu.
f Select the menu or value and confirm with OK:
SETTINGS
HEATING

ELECTRIC BOOSTER HEATER

NUMBER OF STAGES
1
Cooling settings
Material losses
!
Condensation caused by the temperature falling below
the dew point can lead to material losses. The appliance
is therefore approved exclusively for area cooling.
For dew point independent cooling, additional accesso-
ries (CDT 180) are required to ensure that any condensate
is reliably drained away.
f Observe the instructions for the heat pump manager.
Adjusting the heat pump manager settings for area cooling:
f With the MENU key, call up the main menu.
f Select the menu or value and confirm with OK:
SETTINGS
COOLING

COOLING

STANDARD SETTING

COOLING CAPACITY

ACTIVE COOLING

AREA COOLING

SET FLOW TEMPERATURE

FLOW TEMP HYSTERESIS

SET ROOM TEMPERATURE
Value
PARALLEL OPERA-
TION
Value
2
Value
ON
system specific
ON
system specific
system specific
system specific
HSBC 180 Plus | HSBC 180 S Plus |
41