BTL5-S1_ _-M_ _ _ _-J-DEXA/B-K_ _
Micropulse Transducer - Rod Style
1
Safety Advisory (cont.)
1.5.
conformity
The transducers have been ap-
proved with certificate number
. The current
issue of the certificate and further
information can be found in the
"Certified Equipment Scheme"
section at www.iecex.com.
1.5.
Special conditions
Symbol "X"
The "X" symbol indicates special
conditions which must be ob-
served for safe use:
– Extended ambient temperature
range –40°C to +60°C
– Impact resistance test up to 4
Joules for low mechanical sus-
ceptibility
– The outer rod is to be protected
from wear and damage
– The connection cable must be
routed in a permanent location
and sufficiently protected
against damage. An additional
clamp must protect against
tension and rotary loads
– The exposed wire ends must
be connected outside the haz-
ardous zone or within an ap-
proved housing
1.5.
Operator documents
Zone classification in the system
is the responsibility of the operator
and must be documented in an
explosion protection document in
accordance with Directive 1999/
92/EC.
We expressly recommend includ-
ing the user's guide in the
operator's documentation. For
safety reasons, it must be taken
over completely and without any
changes.
1.6
Scope
This guide applies to the model
BTL5-
....
transducer.
An overview of the various models
can be found in section 6 Versions
(indicated on product label).
Flameproof enclosure
english
3