BTL5-S1_ _-M_ _ _ _-J-DEXA/B-K_ _
Micropulse Transducer - Rod Style
4
Wiring
Important wiring note:
➥ ➥ ➥ ➥ ➥
8
english
Control and data signals
BTL5-S1...
Wire color
+Clk
YE yellow
–Clk
PK pink
+Data
GY grey
–Data
GN green
Supply voltage (external)
BTL5-S1...
Wire color
+24 V
BN brown
GND
BU blue
not used
WH white *
* The white lead must be tied
on the control side to the
terminal with the blue lead.
Table 4-1: Wiring
+Clk
–Clk
+Data
–Data
+24 V
GND
BTL5-S1...
-K_ _
Potential compensation
as per DIN EN 60079-14
Fig 4-1: BTL5-S1...-K_ _ with controller, wiring example
Flameproof enclosure
When routing the cable between
the transducer, controller and
power supply, avoid proximity to
high voltage lines to prevent noise
coupling. Especially critical is in-
ductive noise caused by AC har-
monics (e.g. from phase-control
devices), against which the cable
shield provides only limited protec-
tion.
Position information is sent over the
RS 485/422 interface as synchro-
nous serial data (SSI) to the host
controller. High noise immunity is
assured by the differential drivers
used for sending and receiving sig-
nals.
Cable length max. 400 m. The
clock frequency is a function of the
cable length:
Cable length
Clock frequency
< 25 m
< 1000 kHz
< 50 m
< 500 kHz
< 100 m
< 400 kHz
< 200 m
< 200 kHz
< 400 m
< 100 kHz
Table 4-2: Clock frequency vs.
cable length
YE
PK
GY
GN
BN
BU
Controller
WH