1. Fit the Installation Plate
1.
Fit the installation plate
tion plate.
2.
If the wall is made of brick, concrete or the like, drill eight (8) 5mm diameter holes in the wall. Insert
Clip anchor
3.
Fit the installation plate
90
NOTE
Fit the Installation Plate and drill holes in the wall according to the wall structure and
corresponding mounting points on the installation plate. (Dimensions are in "mm" unless
otherwise stated)
40
Over 12 cm from the wall
133
4
56
horizontally on structural parts of the wall with spaces around the installa-
for appropriate mounting screws
on the wall with eight (8) type "A" screws
70
70
750
Indoor unit outline
Installation plate
920
Left rear side refrigerant
pipe hole Ø65
A:780 (< 4.6 kW model)
Wall
Indoor
Fig. 6
.
150 mm or more to ceiling
50
920 (4.6 kW ≤ model < 6.1 kW)
Outdoor
≥5°
.
Installation plate
Over 12 cm
from the wall
Right rear side
refrigerant pipe
hole Ø65