WARNING:
To avoid serious personal injury, always check for gas
leaks any time the propane cylinder is disconnected and
then reconnected.
After installing a 20 lb. propane cylinder, check for leaks
at both the generator and cylinder connection before use.
Make sure the propane hose adaptor is properly con-
nected to the generator and the propane cylinder.
Turn handwheel counterclockwise to open the cylinder
valve.
NOTE: If you hear a rushing sound, immediately turn off
the cylinder valve. This sound means there is a major leak
at the connection. Correct the problem before proceeding.
Using a clean paint brush and a 50/50 mixture of mild
soap and water, brush soapy solution over the connection
at the propane cylinder.
"Growing" bubbles indicate a leak. Close the cylinder
valve and retighten connection.
NOTE: If leaks cannot be stopped, do not try to repair.
Replace the propane cylinder.
If you are not using the generator immediately after the
leak test, close the cylinder valve by turning the valve
clockwise.
SAFETY TIPS WHEN USING A PROPANE
CYLINDER TO FUEL GENERATOR
Before opening the propane cylinder valve, check the
coupling nut for tightness and perform a leak test as
described earlier in this manual.
When generator is not in use, remove the 1 lb. cylinder
or close the 20 lb. cylinder valve.
If the regulator frosts, immediately turn off the generator,
wait 5 minutes for unit to cool, and then remove the 1 lb.
cylinder or close the 20 lb. cylinder valve. This indicates
a problem with the propane cylinder and it should not be
used. Return the cylinder to the supplier.
STARTING THE ENGINE
See Figures 10 - 11.
NOTICE:
On a level surface with the engine off, check the lubricant
level before each use of the generator.
NOTE: If location of generator is not level, the unit may not
start or may shut down during operation.
OPERATION
Unplug all loads from the generator.
Make sure the propane cylinder is tested and installed as
described earlier in this manual. If using a 20 lb. cylinder,
open the cylinder valve completely.
Press the primer button one time for approximately two
seconds.
Pull the recoil starter grip until the engine runs.
NOTE: Do not allow the grip to snap back after starting;
return it gently to its original place.
STOPPING THE ENGINE
See Figure 12.
To stop the engine under normal operating conditions:
Remove any load from the generator.
Press and hold the engine switch until the engine stops.
Remove the 1 lb. cylinder or close the 20 lb. cylinder valve
completely.
To stop the unit quickly in an emergency:
Press and hold the engine switch until the engine stops.
Remove the 1 lb. cylinder or close the 20 lb. cylinder valve
completely.
WARNING:
While operating and storing, keep at least 3 feet of clear-
ance on all sides of this product, including overhead.
Allow a minimum of 30 minutes of "cool down" time
before storage. Heat created by muffler and exhaust
gases could be hot enough to cause serious burns and/
or ignite combustible objects.
MOVING THE GENERATOR
See Figure 13.
Turn off the generator.
Allow 30 minutes of "cool down" time before storing the
machine. Make sure engine and exhaust of unit are cool.
Carry by the carry handle.
Grasp the handle firmly with one hand.
Lift the generator and carry the unit at your side to the
desired location.
Lower the generator until it sits securely on a flat surface.
16 — English