Step
Action/Display Indication
9
I f n e c e s s a r y, c h a n g e " P 0 2 9 8 –
Application" parameter. This change
will affect P0156, P0157, P0158, P0401,
P0404 and P0410 (this last one only if
P0202 = 0, 1 or 2 - V/f modes). The
time and level of the IGBT overload
protection will also be affected.
Press the
key to the next parameter.
10
If necessary, change "P0202 – Control
Type" parameter. This guide will only show
the setting for P0202 = 0 (V/f 60 Hz) or
P0202 = 1 (V/f 50 Hz). Refer to the
programming and troubleshooting
manual for other settings (V/f Adjustable,
V V W or Vector Modes).
Press the
key to the next parameter.
11
If necessary, change "P0398 – Motor
Service Factor" parameter. This change
will affect the current and the time of the
motor overload protection operation.
Press the
key to the next parameter.
Step
12
13
14
Figure 5.1 (cont.): Oriented Start-up
First Time Power-Up and Start-Up
Action/Display Indication
If necessary, change "P0400 – Motor
Rated Voltage" parameter. This change
corrects the output voltage by the factor
"x = P0400/P0296".
Press the
key to the next parameter.
If necessary, change "P0401 – Motor
Rated Current" parameter. This change
will affect P0156, P0157, P0158 and
P0410.
Press the
key to the next parameter.
If necessary, change "P0404 – Motor
Rated Power" parameter. This change
will affect P0410.
Press the
key to the next parameter.
CFW700 | 41