Power Wiring Connections
NOTE: Consult the product wiring diagram
located on the starter enclosure for customized
panels.
• Wire main power input and motor leads to the
appropriate terminals, tightened as indicated in
the
"Specifications" on page
• Use only copper conductors rated at least 167 °F
(75 °C).
• Maintain proper clearances and verify that no
possibility of an electrical short exists between
the power conductors or enclosure.
• Ensure that wires are not under stress and all
insulation is intact.
• Verify voltage input matches label.
• Low voltage and automation system wiring
should be run in a separate conduit.