INSTALLATION
Electrical Installation
I/O Wiring Connections
NOTE: Use 26~14 AWG wire
and torque to 3.5 lb-in for
control wiring.
1. D3/D4/D5 Pilot Device Input:
Connections for a 3-position
(HOA) switch for motor con-
trol.
2. D1/D2 Dry Auto Input: Use
this input to send a run com-
mand to the starter when in
Auto mode. (N.O. dry contact
or transistorized input)
3. O1/O2 Fault Relay
Output: Normally open relay
contacts that closes in the
event of a fault condition.
Rated for 120 VAC, 0.6 A
4. C-/C+ Contactor Output:
Provides a 24 V output to close the contactor when the motor starter is commanded in either Hand
or Auto mode. Once the contactor is closed, the output drops to 2-4 V to maintain contactor closure
while optimizing efficiency. Only for use with a Franklin Electric contactor of the same size with 24
VAC coil (0.875 A Max).
4
Amps
Overload Setting
(Range varies per model)
Pilot
Devices
Dry
Input
Relay
Outputs
Keypad
Contactor
Coil
PCB Power
H1
H4
50
30
70
0
100
%
UNDERLOAD
HAND
Hand
1
Auto
Common
Auto
2
Run
Alarm Lamp
3
Fault
12-250VAC
4
A2
CON
A1
OFF
AUTO
X
X
Normally
Open Input