1) GENERAL INFORMATION
The THALIA BT A80 control panel is supplied by the manufacturer with standard
settings. Any variation must be set using the built-in on-screen programmer.
Its main features are:
-
Control of 1 or 2 24V BT motors
Note: 2 motors of the same type must be used.
-
Electronic torque control with obstacle detection
-
Limit switch control inputs based on motor selected
-
Separate inputs for safety devices
-
Built-in radio receiver rolling code with transmitter cloning.
The board has a terminal strip of the removable kind to make maintenance
or replacement easier. It comes with a series of prewired jumpers to make the
installer's job on site easier.
The jumpers concern terminals: 70-71, 70-72, 70-73. If the above-mentioned
terminals are being used, remove the relevant jumpers.
2) TESTING
The THALIA BT A80 panel controls (checks) the start relays and safety devices
(photocells) before performing each opening and closing cycle.
If there is a malfunction, make sure that the connected devices are working
properly and check the wiring.
3) TECHNICAL SPECIFICATIONS
Power supply
Low voltage/mains insulation
Operating temperature range
Thermal overload protection
Dielectric rigidity
Motor output current
Terminal
L
N
10
11
14
15
20
21
26
27
28
29
41
42
43
44
45
42
43
40
42
43
40
41
42
43
INSTALLATION MANUAL
220-230V 50/60 Hz
> 2MOhm 500V
-20 / +55°C
Software
mains/LV 3750V~ for 1 minute
max. 7.5A+7.5A
Definition
LINE
Single-phase power supply
NEUTRAL
MOT1 +
Connection motor 1. Time lag during closing.
Check connections shown in Fig.E
MOT1 -
MOT2 +
Connection motor 2. Time lag during opening.
Check connections shown in Fig.E
MOT2 -
AUX1 configurable output - Default setting FLASHING LIGHT.
AUX 1-POWERED
2ND RADIO CHANNEL/ SCA GATE OPEN LIGHT/ COURTESY LIGHT command/ ZONE LIGHT command/ STAIR LIGHT/ GATE
CONTACT
OPEN ALARM/ FLASHING LIGHT/ SOLENOID LATCH/ MAGNETIC LOCK/ MAINTENANCE/ FLASHING LIGHT AND MAINTE-
24V
(≤ 1A)
NANCE. Refer to "AUX output configuration" table.
AUX 2 configurable output - Default setting 2ND RADIO CHANNEL Output.
AUX 2 - FREE
2ND RADIO CHANNEL/ SCA GATE OPEN LIGHT/ COURTESY LIGHT command/ ZONE LIGHT command/ STAIR LIGHT/ GATE
CONTACT (N.O.)
OPEN ALARM/ FLASHING LIGHT/ SOLENOID LATCH/ MAGNETIC LOCK.
(24V
/≤ 1A)
Refer to "AUX output configuration" table.
Lock type Logic = 0 - 12V
Lock type Logic = 1 - 12V
Lock type Logic = 2 - 24V
LOCK 12/24V
Lock type Logic = 3 - 24V
Lock type Logic = 4 - Traction lock: active throughout the manoeuvre.
Max.: 1 A for 1S, 0.2 A for the rest of the manoeuvre.
+ REF SWE
Limit switch common
SWC 1
Motor 1 closing limit switch SWC1 (N.C.).
SWO 1
Motor 1 opening limit switch SWO1 (N.C.).
SWC 2
SWO 2
Motor 2 opening limit switch SWO2 (N.C.).
Limit switch control motor 1.
SW 1
For actuators with single-wire limit switch control.
Limit switch control motor 2.
SW 2
For actuators with single-wire limit switch control.
- REF SWE
Limit switch common
SW 1
Limit switch control motor 1.
SW 2
Limit switch control motor 2.
- REF SWE
Encoder power supply, white cable
+ REF SWE
Encoder power supply, brown cable
ENC M1
Engine 1 encoder signal, green cable
ENC M2
Engine 2 encoder signal, green cable
Motor relay switching current
Maximum motor power
Accessories power supply
AUX 1
AUX 2
N° of combinations
Max.n° of transmitters that can be
memorized
Usable transmitter versions:
All ROLLING CODE transmitters compatible with
4) TUBE ARRANGEMENT Fig. A
5) TERMINAL BOARD WIRING Fig. B
WARNINGS - When performing wiring and installation, refer to the standards in
force and, whatever the case, apply good practice principles.
Wires carrying different voltages must be kept physically separate from each other,
or they must be suitably insulated with at least 1mm of additional insulation.
Wires must be secured with additional fastening near the terminals, using devices
such as cable clamps.
All connecting cables must be kept far enough away from the dissipater.
WARNING! For connection to the mains power supply, use a multicore cable
with a cross-sectional area of at least 2x1.5mm
the regulations in force. To connect the motors, use a cable with a cross-sec-
tional area of at least 1.5mm
2
force. The cable must be type H05RN-F at least.
Description
220-230V 50/60 Hz
snap action electric lock output (max 30W). Pulse activated output on each opening.
magnet electric lock output (max 15W). Output Activated with gate closed.
snap action electric lock output (max 30W). Pulse activated output on each opening.
magnet electric lock output (max 15W). Output Activated with gate closed.
10A
180W + 180W (24V
)
24V
(≤ 0.5 A)
24V
safe
NO 24V
powered contact (≤ 1A)
NO contact (24V
/≤ 1A)
4 billion
128
of the kind provided for by
2
of the kind provided for by the regulations in
THALIA BT A80 -
43