4. Connecting the MD5KVR
ATTENTION: For a safe operation, the procedures detailed below should
be carried out with the device Powered-Off.
Use only the accessories / test leads supplied by the manufacturer.
Using accessories / test leads not provided by the manufacturer may
compromise the equipment safety.
Please, do check there is no difference of potential voltages between the
points where the MD5KVR shall be connected to. Please, check the same
between those points and the ground.
At the time of the connection and power-on, the equipment automatically
enters in the voltmeter mode and begins to exhibit the circuit voltage in
the display.
The circuit to be tested must be de-energized to avoid interference in the
measurement. The equipment will block the start of measurement if it
detects a voltage greater than 60 V in the circuit.