Connections
220...240V three-phases supply (L1,L2,L3)
[220...240V single-phase (L,N)]
WITHOUT IT
COMMANDS
ARE NOT
FUNCTIONING
4k7 Ω Ω Ω Ω Ω
RS - 485
NOTE :
The connections stated for the control keys are the most common solution for a NPN control.
Other examples are given on the following page.
L1 (L)
FILTRO
L2 (N)
L3
G
6 + 24V
5
CM - IN
Reversal
1
REV
Run
2
RUN
External alarm
EXTFLT
3
JOG
11
IN4
Alarm reset
IN5
4
7
GND - D
PE (EARTH)
10
13
+10V
Speed reference
14
IN-Analog
15 GND - A
LNK +
8
LNK -
9
—————— QUIXDrive Inverter ——————
BRAKING
RESISTANCE
Ferrite
toroid
R
U
V
W
P E
12
OUT
AN
15
GND - A
18
OUT1 - NO
Multi-function
16
OUT1 - NC
output active with
a running motor
17
OUT1 - CM
TERMINAL BLOCK CONNECTIONS
M
0 / 10V factory-set
programmable analog output.
It is proportional to the output
frequency on the motor.
7-GB