15.3. NETWORK SETTINGS
The VMF-E0R/VMF-E18R thermostats are designed to
communicate with the remote control panel of the
same VMF-E4 family (mandatory accessory).
The serial communications protocol is Modbus and
a TTL network, which is used for the exchange of
information within a small network of fan coil units
between one and six units, of which one is Master and
a maximum of five are Slaves.
The Master fan coil unit is the one connected to the
VMF-E4 control panel, and sets the following points:
Control setpoint.
Operating mode.
Off: Units off.
AUTO: The thermostat maintains the tem-
perature setpoint by changing the fan speed
in Automatic Mode, as a function of the space
temperature relative to the setpoint.
V1: The thermostat maintains the temperature
setpoint by On-Off cycles only using the Mini-
mum Speed of the fan.
V2: The thermostat maintains the tempera-
ture setpoint by On-Off cycles only using the
Medium Speed of the fan.
V3: The thermostat maintains the temperature
setpoint by On-Off cycles only using the Maxi-
mum Speed of the fan.
AUX: The thermostat forces into heating
mode and maintains the temperature setpoint
through the use of radiant heating and convec-
tive heating from the heat exchanger, inhibiting
the ventilation.
Operating season.
Ambient sensor.
The Slave fan coil units cannot operate with different
settings to the Master's.
16. INSTALLATION OF THE FILTER
• Installation
−The unit; with the tip of a tool, pry the upper
hooks of the grill.
−Insert the filter into the internal part of the
intake grille.
−Reassemble the suction grille to the unit; first
insert the lower hooks into the casing then
insert the upper hooks.
−Easily removable, it is supplied in a sealed pack-
age, to be opened only at the time of use.
• Maintenance
Clean frequently. Remove any accumulated
dust with a vacuum cleaner. Use of water or
detergents greatly
20
STAND ALONE application:
ZONE CONTROLLED application
TTL Line
L= max 30 mt.
WARNING:
For further information on the
use and installation of the VMF-E4
control panel refer to the acces-
sory documentation
IUL_R-UL_RIPI. 2307-C6976485_00
Omnia UL_R/UL_RI 27-37
.