Descargar Imprimir esta página

Ecoflam MAX 12 TC O 50-60 Manual Del Usuario página 14

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 42
EN
Start up
­ Setting data table ­ Air regulation
The burner leaves the factory with the following calibration values:
BURNER
CODE
3146832
3146838
The settings above are basic settings. In case of operation at 60 Hz, the burner must be recalibrated by closing the air shutter so as to
reduce the amount of incoming air.
A
B
14
www.ecoflam­burners.com
NOZZLE
gph
Type
spry
2,0
DELAVAN
60°B
2,0
DELAVAN
60°B
MIN
PUMP
BURNER
PRESSURE
OUTPUT
bar
kg/h
12
8,74
10
8,43
MAX
FIRING HEAD 
AIR DAMPER
SETTING
SETTING
Pos.
2
2
Air damper setting (A).
To act on the screw in figure:
• to increase output, turn screwdriver
(Allen key) clockwise
• to reduce output, turn screwdriver (Allen
key) counterclockwise.
Firing head setting (B).
To act on the screw in figure:
• turn Allen key till you reach the
requested value (index 0-4,5).
420011054600
Pos.
5
4,5

Publicidad

loading

Este manual también es adecuado para:

31468323146838