Troubleshooting (continued)
Display
Code
Description
Message
F51
F51 INP1
Unmonitored
F52
BLOCK
eye/edge
F52 INP1
device
F53
CMND
triggered for
F54
3 minutes
F53 INP2
or more on
F55
BLOCK
input 1/2/3/4,
F56
F54 INP2
or blocked
CMND
when door
F57
motion was
F58
F55 INP3
requested
BLOCK
F56 INP3
CMND
F57 INP4
BLOCK
F58 INP4
CMND
Possible
Diagnosis
Causes
Obstruction
Check for obstructions
in doorway
is blocking
unmonitored
eye/edge
device
Improperly
Check system settings
configured
item in the menu to check
input
the device type setting for
the input
Incompatible
INP1/2/3/4 inputs are
device is
compatible with dry-
being used
contact type devices.
Ensure the device being
used is a dry-contact type
device.
Wiring fault to
Check wiring for short or
device
open circuit
Ensure wires are wired into
correct terminals
Damaged
Swap device with known-
device
good device
Damaged
Disconnect unmonitored
powerhead
eye/edge. Open circuit
main board
condition is equivalent to an
unobstructed unmonitored
eye/edge device.
56
Resolution
If obstructions are present, remove
the obstruction
Ensure the device type matches the
device that is actually installed
If the device is incompatible, replace
with one that is, or move the device
to another input which is compatible
with the device
Correct wiring faults
If a known-good device works,
replace the faulty device
If the main board still detects
an obstruction with no device
connected, power cycle the
operator.
If the problem persists, reset to
factory defaults and configure
again.
If problem still persists, replace the
powerhead main board.