Table 1-1 Standard model
Combination outdoor units
Outdoor unit
capacity type
Unit 1
Unit 2
6 ton
072
072
8 ton
096
096
10 ton
120
120
12 ton
144
144
14 ton
168
168
16 ton
192
192
16 ton
192
096
18 ton
216
144
20 ton
240
144
22 ton
264
168
24 ton
288
144
26 ton
312
168
28 ton
336
168
30 ton
360
168
32 ton
384
144
34 ton
408
168
36 ton
432
168
38 ton
456
168
40 ton
480
168
42 ton
504
168
Table 1-2 High heat model
Combination outdoor units
Outdoor unit
capacity type
Unit 1
Unit 2
6 ton
072
072
8 ton
096
096
10 ton
120
120
12 ton
144
072
16 ton
192
096
20 ton
240
120
24 ton
288
096
30 ton
360
120
Table 2 Additional amount of refrigerant based on the liquid pipe diameter and length.
1/4 in.
Liquid pipe diameter
6.4 mm
lbs / ft
0.017
Additional amount
of refrigerant
kg / m
0.025
Table A
Diversity
Correction factory
Less than 135%
1.3
135% or more
1.2
35-EN
Amount of additional
Amount of additional
refrigerant (lbs)
refrigerant (kg)
Unit 3
-
-
2.2
-
-
2.2
-
-
0.0
-
-
2.2
-
-
4.4
-
-
5.5
096
-
4.4
072
-
4.4
096
-
4.4
096
-
6.6
144
-
4.4
144
-
6.6
168
-
8.8
096
096
8.8
144
096
6.6
144
096
8.8
168
096
11.0
144
144
8.8
168
144
11.0
168
168
13.2
Amount of additional
Amount of additional
refrigerant (lbs)
refrigerant (kg)
Unit 3
-
-
2.2
-
-
2.2
-
-
6.6
072
-
4.4
096
-
4.4
120
-
13.2
096
096
6.6
120
120
19.8
3/8 in.
1/2 in.
5/8 in.
3/4 in.
9.5 mm
12.7 mm
15.9 mm
19.1 mm
0.037
0.071
0.108
0.168
0.055
0.105
0.160
0.250
Table 3-1 Additional amount of refrigerant for standard indoor unit type.
Indoor unit capacity type
lbs / unit
Additional amount
of refrigerant
1.0
kg / unit
1.0
Table 3-2 Additional amount of refrigerant for 4-way Cassette type (Model name: MMU-UP***1HP-UL).
0.0
1.0
Indoor unit capacity type
lbs / unit
2.0
Additional amount
of refrigerant
2.5
kg / unit
2.0
Table 3-3 Additional amount of refrigerant for Concealed Duct Medium Static type
2.0
(Model name: MMD-UP***1BHP-UL).
2.0
Indoor unit capacity type
3.0
lbs / unit
Additional amount
2.0
of refrigerant
kg / unit
3.0
4.0
Table 3-4 Additional amount of refrigerant for DX Coil inter face
4.0
(Model name: TCB-IFDMR01UP-UL/RBM-A***1UPVR-UL)
3.0
Indoor unit capacity type
4.0
5.0
Additional amount
lbs / unit
4.0
of refrigerant
kg / unit
5.0
• If the Outside Air Unit (MMD-UP****HFP-UL) is connected, the correction amount refrigerant for Outside Air Unit
6.0
is 0 kg.
Table 4 Refrigerant amount adjustment based on the indoor unit connection capacity.
Diversity
D
1.0
50% ≤ D < 60%
1.0
60% ≤ D < 70%
3.0
70% ≤ D < 80%
2.0
80% ≤ D < 90%
2.0
90% ≤ D < 95%
6.0
95% ≤ D
3.0
Charging of refrigerant
9.0
• Keeping the valve of the outdoor unit, be sure to charge the liquid refrigerant into the service port at the liquid
side.
• If the specifi ed of refrigerant cannot be charged, fully open the valves of the outdoor unit at liquid and gas sides,
7/8 in.
operate the air conditioner in COOL mode, and then charge refrigerant into service port at the L gas side.
22.2 mm
In this time, choke the refrigerant slightly by operating the valve of the canister to charge liquid refrigerant.
• The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradualy.
0.235
0.350
– 18 –
007
009
012
015
018
021
024
027
030
0.44
0.88
0.2
0.4
007
009
012
015
018
024
027
0.44
0.88
0.2
0.4
007
009
012
015
018
021
024
0.88
0.4
007
009
012
015
018
024
027
030
036
ton
0.6
0.8
1
1.25
1.5
2
2.25
2.5
3
0.24 0.32 0.42 0.60 0.72 0.92 1.12 1.20 1.51 1.91 2.11 2.50 3.09 3.97 4.68
0.11 0.15 0.19 0.27 0.33 0.42 0.51 0.54 0.69 0.87 0.96 1.13 1.40 1.80 2.12
Refrigerant amount adjustment
lbs
kg
-9.92
-4.5
-7.72
-3.5
-5.51
-2.5
-3.31
-1.5
-1.10
-0.5
0
0
036
042
048
054
072
096
1.32
2.20
0.6
1.0
030
036
042
048
054
1.32
0.6
030
036
042
048
054
1.32
0.6
048
054
060
072
096
120
4
4.5
5
6
8
10
EN
EN
ID